Multiquip MQ MultiQuip Power DCA85USJ2 Manual do Utilizador Página 38

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
Vista de página 37
PAGE 38 — DCA85USJ2 60 HZ GENERATOR • OPERATION AND PARTS MANUAL — REV. #1 (03/22/11)
OUTPUT TERMINAL PANEL FAMILIARIZATION
OUTPUT TERMINAL PANEL
The Output Terminal Panel (Figure 7) shown below is
located on the right-hand side (left from control panel) of
the generator. Lift up on the cover to gain access to
receptacles and terminal lugs.
NOTICE
Terminal legs “O” and “Ground” are considered bonded
grounds.
OUTPUT TERMINAL FAMILIARIZATION
The “Output Terminal Panel ” (Figure 6) is provided with
the following:
Three 120/240V output receptacles @ 50 amp
Three Circuit Breakers @ 50 amps
Two 120V GFCI receptacles @ 20 amp
Two GFCI Circuit Breakers @ 20 amps
Five Output Terminal Lugs ( U, V, W, O, Ground)
Figure 7. Output Terminal Panel
Vista de página 37
1 2 ... 33 34 35 36 37 38 39 40 41 42 43 ... 101 102

Comentários a estes Manuais

Sem comentários